Electrical connections

 

The steam generator must be connected to the mains by a qualified electrician and in compliance with current regulations.

Output kW Generator connection cable H07RN-F / 60245 IEC 66 mm² 400V-415V 3N~ Fuse A Generator connection cable H07RN-F / 60245 IEC 66 mm² 230V 3~ Fuse A Generator connection cable H07RN-F / 60245 IEC 66 mm² 230V-240V 1N~/2~ Fuse A Room Size m³
3.4 5 x 1.5 3  x  10 4 x 1.5 3  x  10 3 x 2.5  16 1,5 – 2,5 
4.7 5 x 1.5 3  x  10 4 x 2.5 3  x  16 3 x 6.0 25  2,5 – 5
6.0 5 x 1.5 3  x  10 4 x 2.5 3  x  16 3 x 6.0 25  5 – 7
7.7 5 x 2.5 3  x  16 4 x 6 3  x  25 3 x 10  35 7 – 10
9.5 5 x 2.5 3  x  16 4 x 6 3  x  25 3 x 10 - - 10 – 12
12.0 5 x 6 3  x  25 4 x 10 3  x  35 - - - - 12 – 15
14.0 5 x 6 3  x  25 4 x 10 3  x  50 - - - - 15 - 18

MAIN SWITCH

There is a main switch at the bottom of one end of the steam generator, which is used only when the steam room is not to be used for a long period of time. The steam generator's automatic flushing and rinsing function will stop, if the power is switched off.

STEAM GENERATOR'S HEATING ELEMENTS

Teho
Power
Leistung
Vastus / Element / Heizstäbe 230V
1 2 3
6 2000W/SEPD 99 2000W/SEPD 113 2000W/SEPD 99
9.5 5250W/SEPD 116 3500W/SEPD 115 5250W/SEPD 116
12 4250W/SEPD 119 3500W/SEPD 115 4250W/SEPD 119
14 5250W/SEPD 116 3500W/SEPD 115 5250W/SEPD 116

 
 